Página 1 - LAUREATE SERIES

LAUREL Electronics Inc.3183-G Airway Ave, Costa Mesa, CA USA 92626Tel: (714) 434-6131 Fax: (714) 434-3766 Website: www.laurels.comLAUREATE SERIESDP

Página 2 - ORDERING GUIDE

-8-8. FRONT PANEL SETUP KEYSFigure 8.1ALARM 2 STATUSINDICATORMENU KEYThe menu key steps through the various meter parameters that may be selected. Th

Página 3 - CONTENTS

-9-9. SETTING MENU LOCKOUTSFor security and ease of operation, any or all program menu items may be disabled. Eachfunction to be disabled is set to

Página 4 - 1. INTRODUCTION

-10-DIGIT SELECT KEY VALUE SELECT KEY MENU KEY Press to select "0" or "1"for flashing digit2 - Alarm Setup3 - Alarm setpoin

Página 5 - 3. SAFETY CONSIDERATIONS

-11-TRUE RMS SIGNAL CONDITIONERVALUE SELECT KEY MENU KEY DIGIT SELECT KEY TEMPERATURE SIGNAL CONDITIONER InPutInput signal type J°F J°C K°F K

Página 6

-12-DIGIT SELECT KEY VALUE SELECT KEY MENU KEY LOAD CELL SIGNAL CONDITIONER 20.0 50.0 100.0 250.0 500.020, 50, 100, 250, 500 mV

Página 7 - 4.6 J3 DIGITAL INTERFACE

-13-DIGIT SELECT KEY VALUE SELECT KEY MENU KEY 0 Not rate of change 1 Rate x 0.1 2 Rate x 1 3 Rate x 10 4 Rate x 100 5 Rate x 1000 6

Página 8 - 5. MECHANICAL ASSEMBLY

-14- FiLtrFiltering (continued) dEc.PtDecimal point selection(Scale and Offset selected)SCALEScale factor multiplier(not available for tC) OFFStOff

Página 9 - 7. CONNECTORS

-15-DIGIT SELECT KEY VALUE SELECT KEY Select 0 through 9 for flash-ing digit. Decimal location isfixed by dEC.Pt selection.Select 0 through 9

Página 10 - 8. FRONT PANEL SETUP KEYS

-16-DIGIT SELECT KEY VALUE SELECT KEY MENU KEY 0 0 AL1 Band deviation AL2 Band deviation 1 AL1 Hysteresis AL2 Band deviation 2 AL1 B

Página 11 - 9. SETTING MENU LOCKOUTS

-17- 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 000Output filtering 000Baud rate 000000Di

Página 12 - 10. SETUP MENU

ORDERING GUIDEL ...Laureate series meter withscrew terminal connectors.Display Color1 ... DPM with green LED2 ... DPM wi

Página 13 - DC SIGNAL CONDITIONER

-18-0000Meter address for RS-232/RS-485 communication( digit display, address numberof meter)Note: Addresses 1 through 15are denoted by 1 through 9 an

Página 14 - .XXX X.XXXX

-19-DIGIT SELECT KEY VALUE SELECT KEY MENU KEY 0 Enabled 1 Disabled 0 Enabled 1 Disabled 0 Enabled 1 Disabled 0 Enabled 1 Disabled

Página 15

-20-11. DC VOLTS & AMPS11.1 RANGE JUMPER SELECTIONSFigure 11.1 DC Signal Conditioner11.2 MENU SELECTIONWhenever the scale factor is 1.0 and offset

Página 16

-21-DIGIT SELECT KEY VALUE SELECT KEY Press the key todisplay SEtuP. (Basic setup)See Section 9, Page 10 fordetailed description of selec-tions

Página 17

-22-12. PROCESS SIGNAL INPUTS12.2 MENU SELECTIONDisplay in engineering units is most easily programmed using the coordinates of 2 points. Thereare two

Página 18

To set up the range using coordinates of 2 points, values for low signal input, low display, highsignal input and high display are entered. The follo

Página 19

-24-DIGIT SELECT KEY VALUE SELECT KEY Press the key to displayHi rd (Desired meter readingat high signal input).Press to display valueand selec

Página 20

-25-Press the key to displayInPut (Input type selection).Note: Selection of input type& range must match jumperselection in Section 13.1.Press

Página 21

-26-14. Pt100 RTD'S14.1 RANGE JUMPER SELECTIONDIGIT SELECT KEY VALUE SELECT KEY Press to select short.Press the key to displayInPut (Inpu

Página 22 - 11. DC VOLTS & AMPS

14.3 MENU SELECTIONSThe following example is setup for a 4-wire DIN RTD. When setting up the meter, it may benecessary to enable some of the menu ite

Página 23

CONTENTS1. INTRODUCTION ... 22. RECEIVING AND UNPA

Página 24 - 12. PROCESS SIGNAL INPUTS

-28-Press until rAtio (Ratio-metric operation) is dis-played.15 STRAIN GAUGES AND POTENTIOMETERSDIGIT SELECT KEY VALUE SELECT KEY Press the k

Página 25 - 1 2 3 4 5

-29-Press the key to displaydEcPt (Decimal point).Press to display decimalpoint location.Use to set digit values andset to .00000 ( 0mV

Página 26 - 13. THERMOCOUPLES

-30-16. AC (RMS) VOLTS & AMPSThis section provides basic setup instructions for true RMS voltage or current monitoring. An RMSsignal conditioner

Página 27

-31-Press the key to displayInPut (Input type selection).Note: Selection of input type& range must match jumperselection in Section 16. 1.Pres

Página 28 - 14. Pt100 RTD'S

-32-17. LOAD CELLS AND MICROVOLT INPUTSThis section provides setup instructions for use as a microvoltmeter or with load cells and straingauges. 10

Página 29

-33-MENU KEY DIGIT SELECT KEY VALUE SELECT KEY Press to display decimalpoint location.Press the key todisplay dEcPt (Decimalpoint).Press

Página 30

-34-18. DUAL ALARM OUTPUTS18.1 OPERATING MODE MENU SELECTIONWhen setting up the meter, it may be necessary to enable some of the menu items. See Sec

Página 31

18.3 BAND DEVIATIONWhen deviation is selected from the setup menu, a value is entered for the amount of deviationrequired. This value represents the n

Página 32 - 16. AC (RMS) VOLTS & AMPS

19. ANALOG OUTPUTThe analog output option provides a 0 to 20mA and a 0 to 10Vdc linear signal derived from thedisplayed reading. The low signal outpu

Página 33

20. RS-232 AND RS-485 INTERFACE20. 1 OPERATING MODE MENU SELECTIONThe following menu items are accessible only with an RS-232 or RS-485 option insta

Página 34

1. INTRODUCTIONThis series of panel instruments is a versatile, cost effective solution to a wide variety ofmonitoring and control applications. Thes

Página 35

-38-15. RS-232 AND RS-485 INTERFACE15. 1 JUMPER SELECTIONSRS232 InterfaceJumper g - installed for normal operationJumper h - installed when used as

Página 36 - 18. DUAL ALARM OUTPUTS

-39-21. 2 BCD OUTPUT LEVELSThe BCD option provides isolated, buffered, stored, 3-state parallel outputs that are selectablefor either 0 to 5V logic le

Página 37

22. 5, 10 AND 24 VDC EXCITATION OUTPUTSacbdefhgFigure 22. 1 - Power Supply-40-22. 2 SELECTION OF OTHER JUMPERSJumper ' a ' - F

Página 38 - 19. ANALOG OUTPUT

-41-23. DIGITAL INPUTSPress the key untilSEtup (Basic meter setup) isdisplayed.Press to display status.Press again to selectdigit. Selec

Página 39

-42-24. CALIBRATIONAll ranges of the meter have been digitally calibrated at the factory prior to shipment. Thecalibration equipment is certified to

Página 40

-43-ACCURACYDC AmperesVOLTAGERANGE200.00 mV2.0000 V20.000 V200.00 V660.0 V10 uV100 uV1 mV10 mV100 mV1 G1 G1 M1 M1 MRESOLUTIONINPUTOHMSERRORAT 25°CDC V

Página 41 - 21. PARALLEL BCD OUTPUT

Span Tempco... 0.003% of reading/°CLoad Cell Meter only...

Página 42

-45-IsolationCoil to Contacts ...Safety-rated to 250Vac, 4.2kVp per High Voltage TestBetween Open Contacts...

Página 43 - .XXX X.XXXX

Rev P 11/06Copyright 1992-2006 Laurel Electronics, Inc.WARRANTYLaurel Electronics Inc. warrants its products against defects in materials or workmansh

Página 44 - 25. SPECIFICATIONS

-3-2. RECEIVING AND UNPACKINGYour meter was carefully tested and inspected prior to shipment. Should the meter be damagedin shipment, notify the frei

Página 45

4. CONNECTOR WIRING INFORMATION4.1 CONNECTOR LOCATIONThe connectors are the screw terminals that plug into the mating jack mounted on the printedcircu

Página 46

-5-4.4 J4 - ANALOG OUTPUTLOAD CELL METER-10 V EXCITATION-SENSE-SIGNAL+SIGNAL+10 V EXCITATION+SENSE4.5 J 2 - DUAL SETPOINT CONTROLLER4.3 J5 - SIGNAL IN

Página 47

-6-5.3 REASSEMBLING THE METERReverse the preceding procedures to reinstall the meter in the case. After the meteris in the case, insert the bottom ta

Página 48 - Rev P 11/06

-7-FRONT VIEWMounting PawlTOP VIEWJ1 J2 J3 J4 J548mm(1.89in)96mm(3.78in)J1 J2 J3 J4 J5102mm(4.02in)5mm(0.1